Selection Guide

Unless otherwise specified, all load currents indicated on the Hangwang relay case are for resistive loads. Under the rated switching voltage, the allowable current of inductive loads should not exceed 30% of the rated resistive loads, the allowable current of motor loads should not exceed 20% of the rated resistive loads, the allowable current of lamp loads should not exceed 10% of the rated resistive loads, and the allowable current of capacitive loads should not exceed 5% of the rated resistive loads. In order to ensure the reliability of the product, it is recommended that the contact load current value should not exceed 60% – 70% of the steady state current value under the rated load of the product.

Nature of the loadInrush current
Resistive load1 times the steady-state current
Sodium lamp load1-3 times the steady-state current
Mercury-vapor lamp load3 times the steady state current
Inductive load3-5 times the steady-state current
Motor load3-5 times the steady-state current
Voltage load3-5 times the steady-state current
Incandescent lamp load3-5 times the steady-state current
Capacitive load3-5 times the steady-state current

Description Of Contact Forms

NameDomestic codeInternational  codeStructural form
Conversion typeZC2
Normally openHA3
Normally closedDB4

Switching type:

The center is a moving contact, coil is not energized, the moving contact and one of the static contact is disconnected and the other one is closed, after the coil is energized, the moving contact will move, so that the original disconnected into a closed state, the original closed into a disconnected state, to achieve the purpose of conversion.

Normally open type:

The contacts are open when the coil is not energized and closed when energized.

Normally closed type:

The contacts are closed when the coil is not energized, and the contacts are closed when energized.